操屁精品视频在线播放,黄色视频app下载,久草视频久草中文在线,日韩成人私密一级精品av

CREATE YOUR LISTING

Beijing Starget Chemicals Co.,Ltd

Main products: Mixed Refrigerant (40) R22 Refrigerant Replacement

Home/Products/ROSH r407c blend / mixed refrigerant msds for retrofit existing R-22 systems/

ROSH r407c blend / mixed refrigerant msds for retrofit existing R-22 systems

Update time:2022-02-04 17:18:54
Price:Negotiable
Min Order:1 Ton / Tons
  • 7 days
  • T/T L/C D/P D/A
  • 0 Ton / Tons per Month

Basic Info

Brand NameSTARGET, NeutralPlace of OriginChina

Product Description


Product Description




Delivery Time:15-45 days


ROSH r407c blend / mixed refrigerant msds for retrofit existing R-22 systems



Specifications:
































Physical?properties




Molecular?formula






Mmolecular?weight




86.20?





Boiling?point?101.3KPa(℃)




-43.80?





Freezing?point?101.3KPa?(℃)









Density?30℃(kg/m3)




1129.30?





Critical?temperature?(℃)




87.30?





Critical?pressure?(MPa)




4.63?





ODP




0.00?





GWP




1700.00?





















Quality?index




Purity




≧99.8%




Water?content




≦0.001%




Acidity




≦0.00001%




Evaporation?residue




≦0.01%




Chloride?content




≦0.0001%




Appearance




Colorless?and?clear




Odor




?Odorless




Retrofit:



R-407C can be used to retrofit existing R-22 systems in positive displacement, direct expansion refrigeration, and air conditioning equipment. R-407C should not be used in centrifugal chillers or other equipment that uses a flooded evaporator due, to its high temperature glide.




Retrofit Procedure

1. Establish baseline performance. Note the oil type in use and any system operating data (if system is operating properly). Check for existing leaks and identify any needed repairs.

2. Recover the existing refrigerant charge (DO NOT vent to atmosphere). Weigh the amount of refrigerant removed.

3. Drain existing oil from the compressor sump, suction line accumulators, etc. Record the amount of oil removed. Add an equivalent amount of OEM recommended POE oil.

4. Recharge the system with the recovered R-22 charge and run the system (at least 1 hour) to circulate the new lubricant.

5. Recover the R-22 charge again and check the residual oil content of the lubricant. The amount of the original lubricant in the POE must be less than 5%.

6. Repeat steps 3 – 5, as needed, until the required oil purity level is reached. Once the oil flushes are completed, standard maintenance should be conducted (i.e. filter-drier change, leak repairs).

7. Evacuate the system (less than 500 microns) and ensure it maintains a vacuum. If vacuum is lost, it may indicate that leaks are present in the system.

8. Charge system with R-407C refrigerant. Remove refrigerant as liquid only from cylinder. The initial charge weight should be approximately 90% of the standard charge for R-22, charging up to 95% if necessary.

9. Adjust TXV set point and/or refrigerant charge to achieve the desired superheat. Low side pressure control settings may also need to be adjusted.

10. Monitor oil level in the compressor. If necessary, adjust oil amount to attain normal operating level(mid-sight glass).

11. Label system clearly, indicating the type and amounts of system refrigerant and oil.



Applications:

Applications include residential and commercial air conditioning systems, non-flooded evaporator chillers, and some commercial refrigeration systems. Since R-407C has similar properties to R-22, it is possible (with modifications) to use it in the same equipment designed for R-22 today.



Competitive Advantage:

1.R407c of all specifications

2.OEM is accepted

3.Purity 99.8%

4.Certifications of

SGS/ROSH/PONY/ISO9001/ISO14001/ISO169

?



Recommended Products

Recently Viewed

Contact Us

  • Beijing Starget Chemicals Co.,Ltd

Copyright ? www.525022.com